Purge calculator: how much inert gas to reach a target oxygen

Enter the vessel volume, starting and target oxygen and the purge flow. The result is the inert gas needed and the time, assuming perfect mixing.

Quick answer

With ideal mixing, oxygen falls exponentially as inert gas is added: the number of vessel volumes needed is the natural log of the starting concentration divided by the target. Bringing 21 % down to 1 % takes about 3.0 vessel volumes; down to 0.1 % takes about 5.3. Real vessels need more if they do not mix well.

Updated 2 November 2026 · Figures from Sarvesh datasheets

Vessel volumes of inert gas-
Inert gas needed (m3)-
Purge time (minutes)-

A dilution purge assumes the vessel is perfectly mixed. Displacement purging of a long pipe can need fewer volumes; a vessel with dead pockets can need many more. Always confirm with an oxygen analyser.

How it is calculated

In a well-mixed vessel, each increment of inert gas dilutes the oxygen in proportion to how much oxygen is present. That gives an exponential decay in concentration with the volume of inert gas added.

C(n) = C0 x e^(-n) n = ln(C0 / Cf) time = n x V / flow

Here n counts vessel volumes of inert gas, C0 is the starting concentration and Cf the target.

Worked example

Worked example

A 10 m3 vessel is purged from 20.9 % to 1 % oxygen: n = ln(20.9) = 3.04 vessel volumes, so 30.4 m3 of nitrogen. At 20 m3/h that takes 91 minutes.

Taking the same vessel to 0.5 % needs n = ln(41.8) = 3.73 volumes, about 37 m3 and 112 minutes. Each halving of the target costs about 0.7 more volumes.

The curve flattens: the last decades of oxygen are expensive, which is why the target should come from the limiting oxygen concentration and a safety margin, not from habit.

Limits

Frequently asked questions

How many volumes does it take to purge a tank with nitrogen?

For good mixing, about 3 vessel volumes to go from air to 1 % oxygen and about 5 volumes to reach 0.1 %.

How do I choose the target oxygen for purging?

Start from the limiting oxygen concentration of the flammable material, then subtract a safety margin set by your safety assessment.

Why does my purge take longer than calculated?

Poor mixing, dead legs, leaks or incorrect inert gas flow. An oxygen analyser on the vent shows what is actually happening.

Can I purge to below 100 ppm oxygen?

Yes, but it takes more volumes and the leak tightness of the system becomes the limit, not the purge calculation.